LT Detuned Reactors

   
Series Reactor For Power Factor Correction
Salient Features of SAGAON Reactors :
Specially Designed Bobbins for efficient Cooling
Multiple Conductors for better Heat dissipation
Vacuum Pressure Impregnated for better penetration
Multiple Air Gaps to avoid Flux Fringing
Mechanically Sturdy Design To Withstand Vibrations
Thermal Switch embedded To Withstand Vibrations
Thermal Switch embedded in winding for over temperature Protection
Low Noise

Type :
Detuned, Iron Core, Copper or Aluminum Wound

Range :
From 5 KVAR to 300 KVAR
Filter Factor 5.67 % , 7 % , 14 %

System Voltage : 440 V, 550 V, 690
LT Detuned Reactors
   
Benefits of using SAGAON Reactors :
Increase life of capacitors
Reduce harmonics in Electrical Systems
Avoid over heating of cables of Transformers
Avoid over current during switching of capacitor banks

Technical Specifications :
Standards Followed : IS -5553-1990
Linearity: Standard 1.73 Times on request 2.08 Times.
Insulation Class H as Standard, F on Request
Inductance Value Accuracy within +, - 1.5% Benifits of using SAGAON Reactors:
Increase life of capacitors
Reduce harmonics in Electrical Systems
Avoid over heating of cables of Transformers
Avoid over current during switching of capacitor banks
Termination: For Copper Wound -Nickel Platted Copper busbar for 25 KVAR & above
For Aluminum Wound -Aluminum Lugs
Noise level less than 60 dB at rated load at I meter Distance
Inductance phase within +1.2%
Adequate cushion provided to avoid heating due to leakage flux
 
Transformers Manufacturer
 
Air Cooled Transformers upto 1150 KVA
 

Typical Data Sheet For 440V, 7% Detuned, Copper Wound Reactors
Value
Dimensions (in mm)
Current
Inductance
Weight (in Kg)
Losses
Watts
 
L
W
H
       
10 KVAR 7%
220
130
165
13.2 A
4.64 mH
15
80W
12.5 KVAR 7%
220
130
165
16.6 A
3.71 mH
15
90W
15 KVAR 7%
220
160
165
19.8 A
3.1 mH
20
130W
25 KVAR 7%
225
145
205
33 A
1.86 mH
24
170W
50 KVAR 7%
260
170
230
65.8 A
0.926 mH
35
250W
75 KVAR 7%
300
175
270
99 A
0.618 mH
47
340W
100 KVAR 7%
300
200
265
131.5 A
0.464 mH
58
380W

 

Typical Data Sheet For 440V, 7% Detuned, Aluminium Wound Reactors
Value
Dimensions (in mm)
Current
Inductance
Weight (in Kg)
Losses
Watts
 
L
W
H
       
10 KVAR 7%
220
150
160
13.2 A
4.64 mH
8.7
90W
12.5 KVAR 7%
240
160
165
16.6 A
3.71 mH
10
90W
15 KVAR 7%
230
170
205
19.8 A
3.1 mH
16.3
125W
25 KVAR 7%
250
180
205
33 A
1.86 mH
20
170W
50 KVAR 7%
290
205
235
65.8 A
0.926 mH
27
250W
100 KVAR 7%
340
250
270
131.5 A
0.464 mH
49
380W
   
Our Other Products
1. Transformers : VPI, Cast Resin, Oil Filled
2. Input & Output Reactor for Drives
3. Impedance Bonds For Railway Signalling
4. DC Air Core Reactors for Steel Mills
5. Dual Inductance DC Iron Core Reactors
Transformer  Manufacturer In Pune

 
Dry Type Power Transformers | Special Purpose Transformers | Control Transformers | Reactors | Automatic Voltage Stabilizers | Impedance Bond | Lighting Transformer | LT Detuned Reactors
Home | Quality | Clients | Contact | Feedback | Sitemap
Designed By : MID | Hosted By : GID | Promoted By : PBD